Air at state 1 passes over a cooling coil and leaves at state 2, as shown on the psychrometric sketch in Figure 2 (apparatus dew point 10 °C; dry-air flow 2 kg/s). Take 1 TR = 3.5 kW and neglect the enthalpy of the condensate. Determine (a) the bypass factor of the coil (answer as a number) and (b) the cooling-coil load (answer in TR).